750kW Gas/HVO/Oil Fired Packaged Boiler Plant
-
3030mm x 2438mm x 2599mm
-
3.5 tonnes (approx.)
Need Help?
01622 632 918
Specifications
Description
Environments
3D Tour
Specifications
- Maximum Output: 750kW Gas or Oil
- Boiler: Viessmann
- Burner: Oil
- Oil: Riello RL100
- Gas: RS100
- Pumps: tpd 100-130/4 (twin head) fixed speed
- Temperature Range: 60-90°C
- LTHW Connections: DN100
- Electrical: 32 amp 3 phase
- Gas Connection: 50mm
- Water Connection: 15mm
- Flow Rate: 19.61kg/s and 117kPA
- Dimensions (LxWxH): 3030mm x 2438mm x 2599mm
- Weight: 3.5 tonnes (approx.)
- Pressurisation Plant: Included (500l expansion)
- Telemetry: Trend IQ3 controller with GSM modem reporting
- Variable Temperature: Yes
- Noise: 75 dBA
- Handling Options: HIAB
- HWS Connection: DN40
- HWS Flow Rate: 1 Kg/s
- Max HWS Temperature: 60°C
- Maximum Static: 6 BAR
- CWS Connection: DN40